Sign In | Join Free | My burrillandco.com
Home > 120Vac Online UPS >

Eco Mode Operation 120Vac Online UPS HQ-TX 2 Phase UPS 6-10kVA Isolatated Output PF0.9

    Buy cheap Eco Mode Operation 120Vac Online UPS HQ-TX 2 Phase UPS 6-10kVA Isolatated Output PF0.9 from wholesalers
     
    Buy cheap Eco Mode Operation 120Vac Online UPS HQ-TX 2 Phase UPS 6-10kVA Isolatated Output PF0.9 from wholesalers
    • Buy cheap Eco Mode Operation 120Vac Online UPS HQ-TX 2 Phase UPS 6-10kVA Isolatated Output PF0.9 from wholesalers
    • Buy cheap Eco Mode Operation 120Vac Online UPS HQ-TX 2 Phase UPS 6-10kVA Isolatated Output PF0.9 from wholesalers
    • Buy cheap Eco Mode Operation 120Vac Online UPS HQ-TX 2 Phase UPS 6-10kVA Isolatated Output PF0.9 from wholesalers
    • Buy cheap Eco Mode Operation 120Vac Online UPS HQ-TX 2 Phase UPS 6-10kVA Isolatated Output PF0.9 from wholesalers
    • Buy cheap Eco Mode Operation 120Vac Online UPS HQ-TX 2 Phase UPS 6-10kVA Isolatated Output PF0.9 from wholesalers

    Eco Mode Operation 120Vac Online UPS HQ-TX 2 Phase UPS 6-10kVA Isolatated Output PF0.9

    Ask Lasest Price
    Brand Name : HRD
    Model Number : HQ6KS-TX,HQ6KL-TX,HQ10KS-TX,HQ10KL-TX
    Certification : ISO9001-2008;CE
    Price : 800-990USD/PCS;
    Delivery Time : 4 WEEKS after deposit
    • Product Details
    • Company Profile

    Eco Mode Operation 120Vac Online UPS HQ-TX 2 Phase UPS 6-10kVA Isolatated Output PF0.9


    HQ-TX series 2 phase UPS 6 -10kVA UPS provide 120/240Vac output voltage with output isolation transformer. This powerful online series integrates true double conversion design, DSP technology, and active input power factor correction design to ensure better output voltage conditions, power quality and power performance at all times. Besides, easy-configurable program via LCD panel enhances the flexibility to meet ever-increasing power demand of IT and networked environment.

    Main Features

    o Double-conversion with output isolation transformer

    o DSP technology guarantees high performance

    o Output Power Factor 0.9

    o Wide input voltage range (120-275 VAC)

    o Active input power factor correction 0.99

    o 50Hz/60Hz frequency converter mode

    o Eco mode operation for energy saving (ECO)

    o Emergency power off function (EPO)

    o Generator compatible

    o Charger capacity to 6A for long-run models

    o SNMP/USB/RS-232 communications

    o 3-stage extendable charging design

    oReverse polarity and feedback protections

    o Maintenance bypass( optional)

    o Adjustable battery numbers

    MODELHQ6KS-TXHQ6KL-TXHQ10KS-TXHQ10KL-TX
    PHASE2-phase in / 2-phase out
    CAPACITY6000 VA /5400 W10000 VA / 9000 W
    INPUT
    Voltage Range120-275 VAC (Ph-N) at 50% load ; 180-275 VAC (Ph-N) at 100% load
    Frequency Range46~54 Hz or 56~64 Hz auto sensing
    Power Factor≧0.99 @ 100% Load
    OUTPUT
    Output Voltage120/240 VAC (L-N,L-L)
    AC Voltage Regulation (Batt. Mode)± 1%
    Frequency Range (Synchronized Range)46~54 Hz or 56~64 Hz
    Frequency Range (Batt. Mode)50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
    Current Crest Ratio3:1 (max.)
    Harmonic Distortion≦ 2 % THD (Linear Load), ≦ 5 % THD (Non-linear Load)
    Transfer TimeAC Mode to Batt. ModeZero
    Inverter to BypassZero
    Inverter to ECO< 10ms
    Waveform (Batt. Mode)Pure Sinewave
    EFFICIENCY
    AC Mode90.5%91%
    Battery Mode87%88%
    ECO Mode96%96%
    BATTERY
    Numbers16PCS*12 V / 7 AH16PCS*12 V / 9 AH
    Typical Recharge Time5 hours recover to 90% capacity7 hours recover to 90% capacity
    Charging Current (Max.)

    1.0 A for standard

    6A for long-run model

    1.0 A for standard

    6A for long-run model

    Float Charging Voltage219 VDC
    INDICATORS
    LCD DisplayUPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
    ALARM
    Battery ModeSounding every 4 seconds
    Low BatterySounding every second
    OverloadSounding twice every second
    FaultContinuously sounding
    PHYSICAL
    MachineDimension, DxWxH (mm)500 x 250 x 860500 x 250 x 620500 x 250 x 860500 x 250 x 620
    Net Weight (kgs)61587264
    PackingDimension, DxWxH (mm)680 x 380 x 1074680 x360 x834680 x 380 x 1074680 x360 x834
    Gross Weight (kgs)6561.77668.7
    ENVIRONMENT
    Operation Humidity0-95 % RH @ 0- 40°C (Non-condensing)
    Noise LevelLess than 60dB @ 1 Meter
    MANAGEMENT
    Smart RS-232/USBSupports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, and MAC
    Optional SNMPPower management from SNMP manager and web browser